Alarm Configuration
You can use it to:
- Configure all alarms of IOT equipment and stock parts.
- Check and deal with the problems in time.
Term | Description |
---|---|
Alarm Type | It includes equipment, part and energy usage. |
Alarm Object | All IOT equipment for equipment alarm type. Parts for part alarm type. Meter/equipment/equipment system/location/zone for energy usage alarm type, which will be dependent on the alarm object type. |
Alarm Configuration Status | Activate Now: The alarm will be triggered once it is configured. Then the alarm status will become "Activated". "Activated" refers to the situation where an alarm log will be generated if the configured rule for this alarm is met. Activate Later: The alarm will not be triggered until you activate the alarm. Then the alarm status will become "Not Activated." "Not Activated" means that this alarm has only completed the configuration. Even if the field equipment matches the configured rule, no alarm log will be generated based on these rules. |
Alarm Rule | The rule you configured about the alarm. Each Equipment and Energy Usage alarm supports up to 10 alarm rule groups. Each Part alarm supports up to 50 alarm rule groups.Each alarm rule group supports up to 2 arithmetic rules. |
Alarm Rule Group | If one alarm configured two alarm rule groups named A(with two arithmetic rules named A1 and A2) and B(with one arithmetic rule named B1), then only A1 and A2 are both violated or only B1 and B2 are both violated can the alarm be effective. |
Alarm Notification | It will decide the alarm notification channels. |
Add Alarm - Equipment
Arithmetic Rule | Description |
---|---|
Alarm Object Attribute | All data points attributes of the alarm projects. |
Attributes Dimension | All raw data of the data point with its type as value. |
- Click "Add"
- Input Basic Information and select Equipment as Alarm Type.
Note: You can add multiple alarm objects(up to 20) here. You can optionally fill in the "Notes" optionally. - Add "Alarm Rule"
Note: Alarm Rule Group: The values added here comes from operator on site. Alarm Time Settings: "xx" minutes gap between repeat transmissions. If you select "30", it means you can receive the alarm every 30 minutes after the alarm is triggered. Applied Alarm Time: You can only select today's time. - Select "Alarm Notification"
Note: There are four ways of notification includes Pop-up, SMS, E-mail and App Notification. If you select E-mail, you can only select users with e-mail filled when adding users. If you select Pop-up, you will view it when you logged in our platform after alarms generated. - Click "Submit".
Add Alarm - Part
Arithmetic Rule | Description |
---|---|
Alarm Object Attribute | It is "Quantity" now. |
Attributes Dimension | All raw data of the data point with its type as value. |
- Click "Add"
- Input Basic Information and select Part as Alarm Type.
Note: You can add multiple alarm objects(up to 20) here. You can optionally fill in the "Notes" optionally. - Add "Alarm Rule"
Note: Alarm Rule Group: The values added here comes from operator on site. The same part can be selected in different rule groups. You cannot add two or more same alarm rule group when adding part alarms. These rules are only suit for stock parts. - Select "Alarm Notification"
Note: There are four ways of notification includes Pop-up, SMS, E-mail and App Notification. If you select E-mail, you can only select users with e-mail filled when adding users. If you select Pop-up, you will view it when you logged in our platform after alarms generated. - Click "Submit".
Add Alarm - Energy Usage
Arithmetic Rule | Description |
---|---|
Alarm Period | You can select daily, weekly and monthly |
Alarm Object Attributes | When the alarm object type is monitoring point, you can select electricity, water, gas and thermal; If these types are not associated with monitoring point, you cannot see them. When the alarm object type is meter, you can select its calculated data point; If no data point, you can select nothing. |
Attributes Dimension | Now you can only select usage value. Usage value is the non-interpolated usage value. |
Alarm Value Type | If the alarm period is "Daily", you can select fixed value, previous period, same period last year and average value of last 30 days. If the alarm period is "Weekly/Monthly", you can select fixed value, previous period and same period last year. |
Alarm Value/*Multiplier | When selecting a fixed value, please enter the alarm value; when selecting the previous period /same period last year/last 30 days average, please enter the alarm %multiplier and the alarm rule is to compare the previous period /same period last year/last 30 days average with the value of these values multiplied by the alarm% multiplier. For example: alarm value type=previous period, alarm% multiplier=90, then applied alarm value= previous period×90% |
- Click "Add"
- Input Basic Information and select Energy Usage as Alarm Type.
Note: The alarm object type can be monitoring point,smart meter or ordinary meter. You can add multiple alarm objects(up to 10) here. You can optionally fill in the "Notes" optionally. - Add "Alarm Rule"
- Select "Alarm Notification"
Note: There are four ways of notification includes Pop-up, SMS, E-mail and App Notification. If you select E-mail, you can only select users with e-mail filled when adding users. If you select Pop-up, you will view it when you logged in our platform after alarms generated. Activated alarms will be triggered around 6:00 am everyday. - Click "Submit".
Activate/Pause Alarm
- Click "Activate/Pause" on the Actions button of list page.
- You will view a pop-up and then click "OK".
Note: If the alarm configuration status is "Activated" on the list, you can click "Pause" and then its status will become "Not Activated". If the alarm configuration status is "Not Activated" on the list, you can click "Activate" and then its status will become "Activated".